0.6/1kv Low Voltage LV Aluminum PVC Insulated PVC Sheath Electrical Power Cable1. Operating CharacteristicsRated voltage: 0.6/1(1.2)kV
Max. Permissible continuous operating temperature of conductor: 70° C
Max. Temperature of conductor during short-circuit (5s max. Duration) shall not exceed:
Nominal cross section of conductor ≤ 300mm2: 160° C;
Nominal cross section of conductor >300mm2: 140° C
The ambient temperature under installation should not be lower than: 0 ° C
The bending radius of cable is recommended as following:
For single core cable: Not less than 20 times of the diameter of cable
For multi-core cable: Not less than 15 times of the diameter of cable
2. ApplicationThe cable is used for fixed installations such as electric power distribution networks or industrial installations, which is laid indoors, in tunnel, in cable trench or in conduit, unable to bear external mechanical force.
3. Manufacturing StandardsIEC 60502-1 & Chinese national standard GB/T 12706-2008 We can produce above cables according to popular international standards such as ASTM, BS, DIN, NF &AS/NZ also.
Main technical data of 0.6/1KV, Single core, Aluminum conductor, PVC insulated, double steel tape armored and PVC or PE sheath cables, CABLE CONSTRUCTION 0.6/1KV AL/PVC/DSTA/PVC or PE Cable size | Conductor type | Nominal thickness of PVC insulation (mm) | Nominal thickness of steel tape(mm) | Nominal thickness of PVC sheath(mm) | Approx. cable overall diameter (mm) | Max. D.C resistance @ 200C (Ω/km) |
1x10mm2 | RM | 1.0 | 0.2 | 1.8 | 12.9 | 3.08 |
1x16mm2 | RM | 1.0 | 0.2 | 1.8 | 13.9 | 1.91 |
1x25mm2 | RM | 1.2 | 0.2 | 1.8 | 14.3 | 1.20 |
1x35mm2 | RM | 1.2 | 0.2 | 1.8 | 15.5 | 0.868 |
1x50mm2 | RM | 1.4 | 0.2 | 1.8 | 17.2 | 0.641 |
1x70mm2 | RM | 1.4 | 0.2 | 1.8 | 19.0 | 0.443 |
1x95mm2 | RM | 1.6 | 0.2 | 1.8 | 21.3 | 0.320 |
1x120mm2 | RM | 1.6 | 0.2 | 1.8 | 22.9 | 0.253 |
1x150mm2 | RM | 1.8 | 0.2 | 1.8 | 24.9 | 0.206 |
1x185mm2 | RM | 2.0 | 0.2 | 1.8 | 27.1 | 0.164 |
1x240mm2 | RM | 2.2 | 0.2 | 1.8 | 30.2 | 0.125 |
1x300mm2 | RM | 2.4 | 0.5 | 2.0 | 35.2 | 0.100 |
1x400mm2 | RM | 2.6 | 0.5 | 2.1 | 38.8 | 0.0778 |
1x500mm2 | RM | 2.8 | 0.5 | 2.2 | 43.0 | 0.0605 |
Note: RE= round conductor RM = stranded conductor SM=sectional conductor
Main technical data of 0.6/1KV, two cores, Aluminum conductor, PVC insulated, double steel tape armored and PVC or PE sheath cables, CABLE CONSTRUCTION 0.6/1KV AL/PVC/DSTA/PVC or PE
Cable size | Conductor type | Nominal thickness of PVC insulation (mm) | Nominal thickness of steel tape(mm) | Nominal thickness of PVC sheath(mm) | Approx. cable overall diameter (mm) | Max. D.C resistance @ 200C (Ω/km) |
2x1.5mm2 | RE or RM | 0.8 | 0.2 | 1.8 | 12.9 | 18.1 |
2x2.5mm2 | RE or RM | 0.8 | 0.2 | 1.8 | 13.7 | 12.1 |
2x4mm2 | RE or RM | 1.0 | 0.2 | 1.8 | 15.5 | 7.41 |
2x6mm2 | RE or RM | 1.0 | 0.2 | 1.8 | 16.5 | 4.61 |
2x10mm2 | RM | 1.0 | 0.2 | 1.8 | 19.1 | 3.08 |
2x16mm2 | RM | 1.0 | 0.2 | 1.8 | 21.2 | 1.91 |
2x25mm2 | SM | 1.2 | 0.2 | 1.8 | 18.6 | 1.20 |
2x35mm2 | SM | 1.2 | 0.2 | 1.8 | 20.1 | 0.868 |
2x50mm2 | SM | 1.4 | 0.2 | 1.8 | 22.4 | 0.641 |
2x70mm2 | SM | 1.4 | 0.5 | 2.0 | 26.9 | 0.443 |
2x95mm2 | SM | 1.6 | 0.5 | 2.1 | 30.3 | 0.320 |
2x120mm2 | SM | 1.6 | 0.5 | 2.2 | 32.6 | 0.253 |
2x150mm2 | SM | 1.8 | 0.5 | 2.3 | 35.5 | 0.206 |
2x185mm2 | SM | 2.0 | 0.5 | 2.5 | 39.1 | 0.164 |
2x240mm2 | SM | 2.2 | 0.5 | 2.7 | 43.6 | 0.125 |
2x300mm2 | SM | 2.4 | 0.5 | 2.8 | 47.6 | 0.100 |
Note: RE= round conductor RM = stranded conductor SM=sectional conductor
Main technical data of 0.6/1KV, three cores, Aluminum conductor, PVC insulated, double steel tape armored and PVC or PE sheath cables, CABLE CONSTRUCTION 0.6/1KV AL/PVC/DSTA/PVC or PE
Cable size | Conductor type | Nominal thickness of PVC insulation (mm) | Nominal thickness of steel tape(mm) | Nominal thickness of PVC sheath(mm) | Approx. cable overall diameter (mm) | Max. D.C resistance @ 200C (Ω/km) |
3x1.5mm2 | RE or RM | 0.8 | 0.2 | 1.8 | 13.4 | 18.1 |
3x2.5mm2 | RE or RM | 0.8 | 0.2 | 1.8 | 14.3 | 12.1 |
3x4mm2 | RE or RM | 1.0 | 0.2 | 1.8 | 16.1 | 7.41 |
3x6mm2 | RE or RM | 1.0 | 0.2 | 1.8 | 17.2 | 4.61 |
3x10mm2 | RM | 1.0 | 0.2 | 1.8 | 20.0 | 3.08 |
3x16mm2 | RM | 1.0 | 0.2 | 1.8 | 22.3 | 1.91 |
3x25mm2 | SM | 1.2 | 0.2 | 1.8 | 21.3 | 1.20 |
3x35mm2 | SM | 1.2 | 0.2 | 1.8 | 23.2 | 0.868 |
3x50mm2 | SM | 1.4 | 0.2 | 1.9 | 26.2 | 0.641 |
3x70mm2 | SM | 1.4 | 0.5 | 2.0 | 31.1 | 0.443 |
3x95mm2 | SM | 1.6 | 0.5 | 2.2 | 35.4 | 0.320 |
3x120mm2 | SM | 1.6 | 0.5 | 2.3 | 38.2 | 0.253 |
3x150mm2 | SM | 1.8 | 0.5 | 2.4 | 41.7 | 0.206 |
3x185mm2 | SM | 2.0 | 0.5 | 2.6 | 46.0 | 0.164 |
3x240mm2 | SM | 2.2 | 0.5 | 2.8 | 51.4 | 0.125 |
3x300mm2 | SM | 2.4 | 0.5 | 3.0 | 56.5 | 0.100 |
Note: RE= round conductor RM = stranded conductor SM=sectional conductor
Main technical data of 0.6/1KV, 3+1 cores, Aluminum conductor, PVC insulated, double steel tape armored and PVC or PE sheath cables, CABLE CONSTRUCTION 0.6/1KV AL/PVC/DSTA/PVC or PE
Cable size | Conductor type | Nominal thickness of PVC insulation(mm) | Nominal thickness of steel tape(mm) | Nominal thickness of PVC sheath (mm) | Approx. cable overall diameter (mm) | Max. D.C resistance @ 200C (Ω/km) |
Phase core | Earth core | Phase core | Earth core | Phase core | Earth core |
3x2.5+1.5mm2 | RE | RE | 0.8 | 0.8 | 0.2 | 1.8 | 14.9 | 12.1 | 18.1 |
3x4+2.5mm2 | RE | RE | 1.0 | 0.8 | 0.2 | 1.8 | 16.7 | 7.41 | 12.1 |
3x6+4mm2 | RE | RE | 1.0 | 1.0 | 0.2 | 1.8 | 18.2 | 4.61 | 7.41 |
3x10+6mm2 | RM | RE | 1.0 | 1.0 | 0.2 | 1.8 | 20.8 | 3.08 | 4.61 |
3x16+10mm2 | RM | RM | 1.0 | 1.0 | 0.2 | 1.8 | 23.5 | 1.91 | 3.08 |
3x25+16mm2 | SM | RM | 1.2 | 1.0 | 0.2 | 1.8 | 24.2 | 1.20 | 1.91 |
3x35+16mm2 | SM | RM | 1.2 | 1.0 | 0.2 | 1.8 | 25.9 | 0.868 | 1.91 |
3x50+25mm2 | SM | SM | 1.4 | 1.2 | 0.5 | 2.0 | 30.5 | 0.641 | 1.20 |
3x70+35mm2 | SM | SM | 1.4 | 1.2 | 0.5 | 2.1 | 33.9 | 0.443 | 0.868 |
3x95+50mm2 | SM | SM | 1.6 | 1.4 | 0.5 | 2.3 | 38.5 | 0.320 | 0.641 |
3x120+70mm2 | SM | SM | 1.6 | 1.4 | 0.5 | 2.4 | 41.8 | 0.253 | 0.443 |
3x150+70mm2 | SM | SM | 1.8 | 1.4 | 0.5 | 2.5 | 45.0 | 0.206 | 0.443 |
3x185+95mm2 | SM | SM | 2.0 | 1.6 | 0.5 | 2.7 | 49.9 | 0.164 | 0.320 |
3x240+120mm2 | SM | SM | 2.2 | 1.6 | 0.5 | 2.9 | 55.5 | 0.125 | 0.253 |
3x300+150mm2 | SM | SM | 2.4 | 1.8 | 0.5 | 3.1 | 61.0 | 0.100 | 0.206 |
Note: RE= round conductor RM = stranded conductor SM=sectional conductor
Main technical data of 0.6/1KV, four cores, Aluminum conductor, PVC insulated, double steel tape armored and PVC or PE sheath cables
CABLE CONSTRUCTION 0.6/1KV AL/PVC/DSTA/PVC or PE
Cable size | Conductor type | Nominal thickness of PVC insulation (mm) | Nominal thickness of steel tape(mm) | Nominal thickness of PVC sheath(mm) | Approx. cable overall diameter (mm) | Max. D.C resistance @ 200C (Ω/km) |
4x1.5mm2 | RE or RM | 0.8 | 0.2 | 1.8 | 14.2 | 18.1 |
4x2.5mm2 | RE or RM | 0.8 | 0.2 | 1.8 | 15.1 | 12.1 |
4x4mm2 | RE or RM | 1.0 | 0.2 | 1.8 | 17.2 | 7.41 |
4x6mm2 | RE or RM | 1.0 | 0.2 | 1.8 | 18.5 | 4.61 |
4x10mm2 | RM | 1.0 | 0.2 | 1.8 | 21.6 | 3.08 |
4x16mm2 | RM | 1.0 | 0.2 | 1.8 | 24.1 | 1.91 |
4x25mm2 | SM | 1.2 | 0.2 | 1.8 | 23.8 | 1.20 |
4x35mm2 | SM | 1.2 | 0.2 | 1.8 | 25.9 | 0.868 |
4x50mm2 | SM | 1.4 | 0.5 | 2.0 | 31.4 | 0.641 |
4x70mm2 | SM | 1.4 | 0.5 | 2.1 | 35.0 | 0.443 |
4x95mm2 | SM | 1.6 | 0.5 | 2.3 | 39.9 | 0.320 |
4x120mm2 | SM | 1.6 | 0.5 | 2.4 | 43.1 | 0.253 |
4x150mm2 | SM | 1.8 | 0.5 | 2.6 | 47.3 | 0.206 |
4x185mm2 | SM | 2.0 | 0.5 | 2.8 | 52.3 | 0.164 |
4x240mm2 | SM | 2.2 | 0.5 | 3.0 | 58.4 | 0.125 |
4x300mm2 | SM | 2.4 | 0.5 | 3.2 | 64.3 | 0.100 |
Note: RE= round conductor RM = stranded conductor SM=sectional conductor
Main technical data of 0.6/1KV, five cores, Aluminum conductor, PVC insulated, double steel tape armored and PVC or PE sheath cables , CABLE CONSTRUCTION 0.6/1KV AL/PVC/DSTA/PVC or PE
Cable size | Conductor type | Nominal thickness of PVC insulation (mm) | Nominal thickness of steel tape(mm) | Nominal thickness of PVC sheath(mm) | Approx. cable overall diameter (mm) | Max. D.C resistance @ 200C (Ω/km) |
5x1.5mm2 | RE or RM | 0.8 | 0.2 | 1.8 | 15.0 | 18.1 |
5x2.5mm2 | RE or RM | 0.8 | 0.2 | 1.8 | 16.1 | 12.1 |
5x4mm2 | RE or RM | 1.0 | 0.2 | 1.8 | 18.5 | 7.41 |
5x6mm2 | RE or RM | 1.0 | 0.2 | 1.8 | 19.8 | 4.61 |
5x10mm2 | RM | 1.0 | 0.2 | 1.8 | 23.3 | 3.08 |
5x16mm2 | RM | 1.0 | 0.2 | 1.8 | 26.2 | 1.91 |
5x25mm2 | SM | 1.2 | 0.2 | 1.8 | 26.1 | 1.20 |
5x35mm2 | SM | 1.2 | 0.5 | 2.0 | 30.7 | 0.868 |
5x50mm2 | SM | 1.4 | 0.5 | 2.1 | 34.6 | 0.641 |
5x70mm2 | SM | 1.4 | 0.5 | 2.3 | 38.9 | 0.443 |
5x95mm2 | SM | 1.6 | 0.5 | 2.5 | 44.4 | 0.320 |
5x120mm2 | SM | 1.6 | 0.5 | 2.6 | 47.9 | 0.253 |
5x150mm2 | SM | 1.8 | 0.5 | 2.8 | 52.6 | 0.206 |
5x185mm2 | SM | 2.0 | 0.5 | 2.9 | 57.9 | 0.164 |
5x240mm2 | SM | 2.2 | 0.5 | 3.2 | 65.0 | 0.125 |
5x300mm2 | SM | 2.4 | 0.5 | 3.4 | 71.6 | 0.100 |
Note: RE= round conductor RM = stranded conductor SM=sectional conductor
Main technical data of 0.6/1KV, 4+1 cores, Aluminum conductor, PVC insulated, double steel tape armored and PVC or PE sheath cables, CABLE CONSTRUCTION 0.6/1KV AL/PVC/DSTA/PVC or PE
Cable size | Conductor type | Nominal thickness of PVC insulation(mm) | Nominal thickness of steel tape(mm) | Nominal thickness of PVC sheath (mm) | Approx. cable overall diameter (mm) | Max. D.C resistance @ 200C (Ω/km) |
Phase core | Earth core | Phase core | Earth core | Phase core | Earth core |
4x2.5+1.5mm2 | RE | RE | 0.8 | 0.8 | 0.2 | 1.8 | 15.9 | 12.1 | 18.1 |
4x4+2.5mm2 | RE | RE | 1.0 | 0.8 | 0.2 | 1.8 | 18.0 | 7.41 | 12.1 |
4x6+4mm2 | RE | RE | 1.0 | 1.0 | 0.2 | 1.8 | 19.6 | 4.61 | 7.41 |
4x10+6mm2 | RM | RE | 1.0 | 1.0 | 0.2 | 1.8 | 22.6 | 3.08 | 4.61 |
4x16+10mm2 | RM | RM | 1.0 | 1.0 | 0.2 | 1.8 | 25.6 | 1.91 | 3.08 |
4x25+16mm2 | SM | RM | 1.2 | 1.0 | 0.2 | 1.8 | 26.6 | 1.20 | 1.91 |
4x35+16mm2 | SM | RM | 1.2 | 1.0 | 0.2 | 1.9 | 28.7 | 0.868 | 1.91 |
4x50+25mm2 | SM | SM | 1.4 | 1.2 | 0.5 | 2.1 | 33.8 | 0.641 | 1.20 |
4x70+35mm2 | SM | SM | 1.4 | 1.2 | 0.5 | 2.3 | 37.8 | 0.443 | 0.868 |
4x95+50mm2 | SM | SM | 1.6 | 1.4 | 0.5 | 2.4 | 42.8 | 0.320 | 0.641 |
4x120+70mm2 | SM | SM | 1.6 | 1.4 | 0.5 | 2.6 | 46.6 | 0.253 | 0.443 |
4x150+70mm2 | SM | SM | 1.8 | 1.4 | 0.5 | 2.7 | 50.4 | 0.206 | 0.443 |
4x185+95mm2 | SM | SM | 2.0 | 1.6 | 0.5 | 2.9 | 55.9 | 0.164 | 0.320 |
4x240+120mm2 | SM | SM | 2.2 | 1.6 | 0.5 | 3.1 | 62.2 | 0.125 | 0.253 |
4x300+150mm2 | SM | SM | 2.4 | 1.8 | 0.5 | 3.3 | 68.4 | 0.100 | 0.206 |
Note: RE= round conductor RM = stranded conductor SM=sectional conductor