15kv Aluminum Stw Cable for Size of 3X70mm2:
1. CE, ISO 9001 Certificaes
2. More than 23 years experiences
3. Professional Manufacturer with Factory located in Henan Province.
4. Quick response and fast delivery.
5. Serve everyone with heart and soul.
brief description
15kv Aluminum Cable
15kv armored cable
15kv power cable 3x70mm
8.7/15kV AL/XLPE/SWA/PVC(or PE) Power Cable
1. Description
Construction: Compacted stranded circular aluminum conductor, extruded semi-conducting compound as conductor shield, cross-linked polyethylene (XLPE) insulation, semi-conducting compound as insulation shield, copper tape or combination of copper wire and tape as metallic screen, three cores assembled together with non-hygroscopic polypropylene filler, wrapped with binder tape, PVC inner covering as armoring bedding, galvanized steel wire
armored, PVC or PE outer sheath.
Chinese Type | Description | Core qty | Conductors range |
YJLV32 | Aluminum conductor, XLPE insulation, Steel Wire Armored, PVC outer sheath Power Cable | 1 or 3 | 25~800mm2 |
YJLV33 | Aluminum conductor, XLPE insulation, Steel Wire Armored, PE outer sheath Power Cable | 1 or 3 | 25~800mm2 |
ZA-YJLV32 ZB-YJLV32 ZC-YJLV32 | Aluminum conductor, XLPE insulation, Steel Wire Armored flame- retardant Power Cable | 1 or 3 | 25~800mm2 |
WDZA-YJLY33 WDZB-YJLY33 WDZC-YJLY33 | Aluminum conductor, XLPE insulation, Steel Wire Armored Low Smoke Halogen Free or Zero Halogen (LSHF or LSZH) flame-retardant Power Cable | 1 or 3 | 25~800mm2 |
2. Operating Characteristics
Rated voltage U0/U(Um): 8.7/15(17.5)kV
U0 is the rated power frequency voltage between conductor and earth or metallic screen for which the cable is designed; U is the rated power frequency voltage between conductors for which the cable is designed;
Um is the maximum value of the "highest system voltage" for which the equipment may be used.
Max. permissible continuous operating temperature of conductor: 90 °C
Max. temperature of conductor during short-circuit (5s max. duration) shall not exceed: 250 °C The ambient temperature under installation should not be lower than: 0 °C
The bending radius of cable is recommended as following:
For single core cable: not less than 15 times of the diameter of cable
For three core cable: not less than 12 times of the diameter of cable
When the armored single core cable used for Alternative Current(AC) system, the armoring material should be non- magnetic.
3. Application
The cable is used for fixed installations such as electric power distribution networks or industrial installations, which is laid indoors, outdoors, in tunnel, in cable trench, or direct in ground, able to bear external mechanical force and certain pulling force.
4. Manufacturing Standards
IEC 60502-2 and Chinese National Standard GB/T 12706-2008
We can produce above cables according to popular international standards such as ASTM,BS,DIN,NF &AS/NZ also.
5. Main technical data
5.1 Main technical data of 8.7/15KV, Single core, Aluminum conductor, XLPE insulated, galvanized steel wire armored and PVC or PE sheath cable
CABLE CONSTRUCTION: 8.7/15KV AL/XLPE/SWA/PVC or PE
Size | Nominal thickness of XLPE insulation(mm) | Approx. thickness of copper tape screen (mm) | Approx. diameter of armoring steel wire(mm) | Nominal thickness of PVC or PE(mm) | Approx. overall diameter of finished cable(mm) | Max. conductor D.C resistance @ 200C (Ω/km) |
1x25mm2 | 4.5 | 0.12 | 1.6 | 1.8 | 28.2 | 1.20 |
1x35mm2 | 4.5 | 0.12 | 1.6 | 1.9 | 29.4 | 0.868 |
1x50mm2 | 4.5 | 0.12 | 1.6 | 1.9 | 30.5 | 0.641 |
1x70mm2 | 4.5 | 0.12 | 1.6 | 1.9 | 32.2 | 0.443 |
1x95mm2 | 4.5 | 0.12 | 2.0 | 2.0 | 34.8 | 0.320 |
1x120mm2 | 4.5 | 0.12 | 2.0 | 2.1 | 36.4 | 0.253 |
1x150mm2 | 4.5 | 0.12 | 2.0 | 2.1 | 38.0 | 0.206 |
1x185mm2 | 4.5 | 0.12 | 2.0 | 2.2 | 39.6 | 0.164 |
1x240mm2 | 4.5 | 0.12 | 2.0 | 2.3 | 42.4 | 0.125 |
1x300mm2 | 4.5 | 0.12 | 2.0 | 2.3 | 44.4 | 0.100 |
1x400mm2 | 4.5 | 0.12 | 2.5 | 2.5 | 49.2 | 0.0778 |
1x500mm2 | 4.5 | 0.12 | 2.5 | 2.6 | 53.1 | 0.0605 |
1x630mm2 | 4.5 | 0.12 | 2.5 | 2.7 | 57.1 | 0.0469 |
1x800mm2 | 4.5 | 0.12 | 2.5 | 2.8 | 61.3 | 0.0369 |
5.2 Main technical data of 8.7/15KV, Single core, Aluminum conductor, XLPE insulated, pure aluminum wire armored and PVC or PE sheath cable
CABLE CONSTRUCTION: 8.7/15KV AL/XLPE/AWA/PVC or PE
Size | Nominal thickness of XLPE insulation(mm) | Approx. thickness of copper tape screen (mm) | Approx. diameter of armoring pure aluminum wire(mm) | Nominal thickness of PVC or PE(mm) | Approx. overall diameter of finished cable(mm) | Max. conductor D.C resistance @ 200C (Ω/km) |
1x25mm2 | 4.5 | 0.12 | 1.6 | 1.8 | 28.2 | 1.20 |
1x35mm2 | 4.5 | 0.12 | 1.6 | 1.9 | 29.4 | 0.868 |
1x50mm2 | 4.5 | 0.12 | 1.6 | 1.9 | 30.5 | 0.641 |
1x70mm2 | 4.5 | 0.12 | 1.6 | 1.9 | 32.2 | 0.443 |
1x95mm2 | 4.5 | 0.12 | 2.0 | 2.0 | 34.8 | 0.320 |
1x120mm2 | 4.5 | 0.12 | 2.0 | 2.1 | 36.4 | 0.253 |
1x150mm2 | 4.5 | 0.12 | 2.0 | 2.1 | 38.0 | 0.206 |
1x185mm2 | 4.5 | 0.12 | 2.0 | 2.2 | 39.6 | 0.164 |
1x240mm2 | 4.5 | 0.12 | 2.0 | 2.3 | 42.4 | 0.125 |
1x300mm2 | 4.5 | 0.12 | 2.0 | 2.3 | 44.4 | 0.100 |
1x400mm2 | 4.5 | 0.12 | 2.5 | 2.5 | 49.2 | 0.0778 |
1x500mm2 | 4.5 | 0.12 | 2.5 | 2.6 | 53.1 | 0.0605 |
1x630mm2 | 4.5 | 0.12 | 2.5 | 2.7 | 57.1 | 0.0469 |
1x800mm2 | 4.5 | 0.12 | 2.5 | 2.8 | 61.3 | 0.0369 |
5.3 Main technical data of 8.7/15KV Single core, Aluminum conductor, XLPE insulated, copper wire screened, galvanized steel wire armored and PVC or PE sheath cable
CABLE CONSTRUCTION: 8.7/15KV AL/XLPE/CWS/SWA//PVC or PE
Size | Nominal thickness of XLPE insulation(mm) | Approx. thickness of copper tape screen (mm) | Nominal diameter of copper wire(mm) | Approx. diameter of steel wire (mm) | Nominal thickness of PVC or PE(mm) | Approx. overall diameter of finished cable(mm) | Max. conductor D.C resistance @ 200C (Ω/km) |
1x25mm2 | 4.5 | 0.12 | 0.9 | 1.6 | 1.9 | 30.0 | 1.20 |
1x35mm2 | 4.5 | 0.12 | 0.9 | 1.6 | 1.9 | 31.0 | 0.868 |
1x50mm2 | 4.5 | 0.12 | 0.9 | 1.6 | 1.9 | 32.1 | 0.641 |
1x70mm2 | 4.5 | 0.12 | 0.9 | 1.6 | 2.0 | 34.0 | 0.443 |
1x95mm2 | 4.5 | 0.12 | 0.9 | 2.0 | 2.1 | 36.6 | 0.320 |
1x120mm2 | 4.5 | 0.12 | 0.9 | 2.0 | 2.1 | 38.0 | 0.253 |
1x150mm2 | 4.5 | 0.12 | 0.9 | 2.0 | 2.2 | 39.8 | 0.206 |
1x185mm2 | 4.5 | 0.12 | 0.9 | 2.0 | 2.2 | 41.4 | 0.164 |
1x240mm2 | 4.5 | 0.12 | 0.9 | 2.0 | 2.3 | 44.0 | 0.125 |
1x300mm2 | 4.5 | 0.12 | 0.9 | 2.5 | 2.4 | 47.4 | 0.100 |
1x400mm2 | 4.5 | 0.12 | 0.9 | 2.5 | 2.5 | 50.8 | 0.0778 |
1x500mm2 | 4.5 | 0.12 | 0.9 | 2.5 | 2.6 | 54.9 | 0.0605 |
1x630mm2 | 4.5 | 0.12 | 0.9 | 2.5 | 2.7 | 58.7 | 0.0469 |
1x800mm2 | 4.5 | 0.12 | 0.9 | 2.5 | 2.9 | 63.1 | 0.0369 |
5.4 Main technical data of 8.7/15KV Single core, Aluminum conductor, XLPE insulated, copper wire screened, pure aluminum wire armored and PVC or PE sheath cable
CABLE CONSTRUCTION: 8.7/15KV AL/XLPE/CWS/AWA//PVC or PE
Size | Nominal thickness of XLPE insulation(mm) | Approx. thickness of copper tape screen (mm) | Nominal diameter of copper wire(mm) | Approx. diameter of aluminum wire (mm) | Nominal thickness of PVC or PE(mm) | Approx. overall diameter of finished cable(mm) | Max. conductor D.C resistance @ 200C (Ω/km) |
1x25mm2 | 4.5 | 0.12 | 0.9 | 1.6 | 1.9 | 30.0 | 1.20 |
1x35mm2 | 4.5 | 0.12 | 0.9 | 1.6 | 1.9 | 31.0 | 0.868 |
1x50mm2 | 4.5 | 0.12 | 0.9 | 1.6 | 1.9 | 32.1 | 0.641 |
1x70mm2 | 4.5 | 0.12 | 0.9 | 1.6 | 2.0 | 34.0 | 0.443 |
1x95mm2 | 4.5 | 0.12 | 0.9 | 2.0 | 2.1 | 36.6 | 0.320 |
1x120mm2 | 4.5 | 0.12 | 0.9 | 2.0 | 2.1 | 38.0 | 0.253 |
1x150mm2 | 4.5 | 0.12 | 0.9 | 2.0 | 2.2 | 39.8 | 0.206 |
1x185mm2 | 4.5 | 0.12 | 0.9 | 2.0 | 2.2 | 41.4 | 0.164 |
1x240mm2 | 4.5 | 0.12 | 0.9 | 2.0 | 2.3 | 44.0 | 0.125 |
1x300mm2 | 4.5 | 0.12 | 0.9 | 2.5 | 2.4 | 47.4 | 0.100 |
1x400mm2 | 4.5 | 0.12 | 0.9 | 2.5 | 2.5 | 50.8 | 0.0778 |
1x500mm2 | 4.5 | 0.12 | 0.9 | 2.5 | 2.6 | 54.9 | 0.0605 |
1x630mm2 | 4.5 | 0.12 | 0.9 | 2.5 | 2.7 | 58.7 | 0.0469 |
1x800mm2 | 4.5 | 0.12 | 0.9 | 2.5 | 2.9 | 63.1 | 0.0369 |
5.5 Main technical data of 8.7/15KV, three cores, Aluminum conductor, XLPE insulated, galvanized steel wire armored and PVC or PE sheath cable
CABLE CONSTRUCTION: 8.7/15KV AL/XLPE/SWA/PVC or PE
Size | Nominal thickness of XLPE insulation(mm) | Approx. thickness of copper tape screen (mm) | Approx. diameter of steel wire (mm) | Nominal thickness of PVC or PE(mm) | Approx. overall diameter of finished cable(mm) | Max. conductor D.C resistance @ 200C (Ω/km) |
3x25mm2 | 4.5 | 0.10 | 2.5 | 2.6 | 54.5 | 1.20 |
3x35mm2 | 4.5 | 0.10 | 2.5 | 2.7 | 56.9 | 0.868 |
3x50mm2 | 4.5 | 010 | 2.5 | 2.8 | 59.7 | 0.641 |
3x70mm2 | 4.5 | 0.10 | 2.5 | 2.9 | 63.7 | 0.443 |
3x95mm2 | 4.5 | 0.10 | 2.5 | 3.0 | 67.6 | 0.320 |
3x120mm2 | 4.5 | 0.10 | 2.5 | 3.1 | 71.1 | 0.253 |
3x150mm2 | 4.5 | 0.10 | 2.5 | 3.2 | 74.8 | 0.206 |
3x185mm2 | 4.5 | 0.10 | 3.15 | 3.4 | 80.2 | 0.164 |
3x240mm2 | 4.5 | 0.10 | 3.15 | 3.6 | 86.1 | 0.125 |
3x300mm2 | 4.5 | 0.10 | 3.15 | 3.7 | 90.9 | 0.100 |
3x400mm2 | 4.5 | 0.10 | 3.15 | 4.0 | 98.7 | 0.0778 |